Selection Guide & Preventive Maintenance Manual for Mining Truck Charging Connectors
Given the complex operating environments of mining charging stations—characterized by high outdoor temperatures, strong radiation, heavy dust, and frequent equipment usage—ensuring the long-term stable and safe operation of charging connectors is critical. This manual provides selection guidelines, installation best practices, and preventive maintenance instructions specifically tailored for mining trucks.
1. Charging Connector Selection
Different mining truck models and battery capacities require specific charging connectors. Please refer to the table below for model selection based on current specifications:
| Rated Current | Model Number | Cable Specifications | Outer Sheath Material | Recommended Continuous Current |
|---|---|---|---|---|
| 250A | WOER-GB-C-D250-02 (Electromagnetic Lock) | 2×80mm² + 1×25mm² + P (4×0.75mm²) + (7×0.75mm²) | TPE | 200A |
| WOER-GB-C-D250-06 (Electromagnetic Lock) | 2×80mm² + 1×25mm² + P (4×0.75mm²) + (7×0.75mm²) | TPE | ||
| WOER-GB-C-D250-07 (Electromagnetic Lock) | 2×80mm² + 1×25mm² + P (4×0.75mm²) + (7×0.75mm²) | TPE | ||
| 300A | WOER-GB-C-D300-06 (Electromagnetic Lock) | 4×50mm² + 1×25mm² + P (4×0.75mm²) + (7×0.75mm²) | TPU | 250A |
| WOER-GB-C-D300-07 (Electromagnetic Lock) | 4×50mm² + 1×25mm² + P (4×0.75mm²) + (7×0.75mm²) | TPU | ||
| 400A | WOER-GB-C-D300-18 (Liquid-Cooled) | 4×60mm² + 1×25mm² + 2×1.5mm² + P (4×0.75mm²) + (9×0.75mm²) | TPU | 350A |
| 400A and above | Liquid-Cooled Connectors recommended | — | — | — |
⚠ Temperature Protection & Derating Strategy:
> 95°C: Charging current derates to 80%.
> 100°C: Charging current derates to 60%.
> 110°C: Charging stops immediately to prevent thermal runaway and ensure safety.
2. Design & Installation Guidelines
To ensure the longevity of the charging cable and connector, proper installation is crucial:
- Cable Routing: It is highly recommended to route the cable from the top of the charging pile, with the cable exiting downwards.
- Bending Angle: The angle between the cable and the pile body should be ≤ 20 degrees.
- Gland Protection: Add a rubber protective sleeve at the cable gland to protect the cable from wear and tear.
- Cable Length: For cables longer than 5 meters, it is recommended to add a spiral wrap (cable guard) to provide additional protection against drag and friction.
- Prohibited Installation: Avoid installations where the cable exits horizontally or bends upwards at a sharp angle (>20°), as this causes strain on the connector and sheath.
3. Usage & Preventive Maintenance Precautions
A. Connector Head & Pin Cleaning
- Chemical Restrictions: DO NOT use chemicals containing ketones, esters, strong acids, alkalis, ammonia water, or bleach for cleaning.
- Cleaning Method: Use a wet wipe dampened with alcohol to gently wipe the surface of the pins. Ensure the pins are free of dust and dirt before use.
- Mining Site Frequency: Due to the heavy dust environment in mining areas, the frequency of pin cleaning must be increased.
B. Cable Handling & Placement
- No Dragging: Never drag, coil, or twist the cable violently. Avoid placing the cable on the ground where it can be run over by heavy machinery.
- Proper Placement: Hang the charging gun properly on the holder when not in use. Ensure the cable is straightened and placed logically.
- Avoid Violent Pulling: Do not pull the cable violently or use it to drag the connector.
- Protect the Sensor/Detector: Prevent the detection mechanism from being damaged by rusted wires, thick cables, or violent pulling.
C. Locking Hook Protection
- No Force: Strictly prohibit violently pressing the locking hook or striking it with any objects. The locking mechanism should be engaged and disengaged smoothly without excessive force.
Issued by: Technical Department / Shenzhen Woer New Energy Electrical Technology Co., Ltd. / (Date: June 12, 2025)